Low subcool low superheat - Subcooling is a measurement of how much the liquid in the condenser cools down before exiting. When the hot gas in the condenser first turns to liquid, its temperature is at the saturation point. This means that the temperature of the liquid as it first forms is at the same temperature at which the refrigerant is condensing — the saturation ...

 
Superheat is a measured value. It is the difference between two temperatures. Superheat is measured as the difference between the actual temperature of the refrigerant vapor and the saturation temperature of the refrigerant at that same point. Superheat on the system's low side can be divided into two types: evaporator …. Lee county fair va

a txv is what maintains superheat for the evap coil. We have taken our superheat measurement. And should know if the superheat is very high no refrigerant is passing the txv. And if it's very low too much is passing. We can then test the txv bulb. Remove it from the system and hold it in your hand to warm it up watch the superheat go down.Freezer superheat and subcooling. Hello HVAC tech I am working on a walk in freezer box temp is -10 degrees. this is a R402A refrigerant unit by Larkin it is a Copeland compressor. My suction temp. at the compressor is 33.7 the saturated temp is -32 at 10 psi. the High side is 215 psi saturated temp 89 degrees and the pipe temp is 91 degrees ...May 22, 2021 · LOW SUPERHEAT LOW SUBCOOLING TXV. Low superheat indicates that there is an excess amount of refrigerant in the evaporator, or the heat load is not sufficient to vaporize the liquid refrigerant to vapor before it moves to the compressor resulting in compressor damage. Plugging of the evaporator coils can also result in low superheat. A subcooling value would be helpful. Reply . 08-02-2013, 09:27 AM #4. Todd Whaley. View Profile ... can mask a low charge scenario. The high head leads to poor heat rejection and the higher pressures can force more of the available refrigerant into the evaporator and show up as normal or high suction pressure with normal or low superheat ...Liquid line restriction. Low pressures, high subcool, high subcool, frost or heavy sweating at restriction, pressure/temperature drop across restriction. Low side restriction. Low. Study with Quizlet and memorize flashcards containing terms like Lack of condenser flow, High evaporator load, Overcharge and more.How to Check Subcooling. Attach the thermometer to the liquid line. This time, near the condenser. Then take the head pressure in Psi and convert it to the temperature on the pressure/temperature chart. Assuming you are dealing with a R22 system, let’s say the head pressure is 260Psi. This will convert to 120F.Subcooling = 11F to 22F; Suction Superheat setpoint for 130-400 = 8F. Subcooling = 11F to 22F; These are measured at the king valve, chiller running at full load, and with all fans running; The subcooling values is based on 95 degree ambient; For high ambient conditions, subcooling will be closer to 11F. For low ambient conditions, subcooling ...Normal Subcooling High Superheat. Find out what it means when your system has normal subcooling but high superheat, and learn how to diagnose and resolve this issue. Normal Subcooling Low Superheat. Learn about the implications of normal subcooling with low superheat and discover the potential causes and solutions for this unique situation.High subcooling shows that the condensing point is occuring earlier in the condenser while low subcooling shows that the condensing point is later in the condenser. Subcooling is used to charge systems with a TXV. Now you can see why knowing what, and why, superheat and subcooling are essential to proper diagnostics and …This thread is in reference to residential split a/c units. I know with a TXV the charge should be checked and/or adjusted according to subcool. If working properly the TXV should pretty much hold the superheat at a constant. But I have seen superheat readings that to me look like the evap coil is being starved. For instance a SH reading above 20 sounds like the charge is low.Liquid line temp 101 degrees and the suction was 49 degrees. The low subcooling and low suction pressure indicate low airflow. The somewhat low deltaT seems to contradict that. Could be a significant amount of air bypassing the coil based on your report, which would account for all of the numbers that you posted.Subcooling should be 5-18 degrees, with higher values when the equipment has a TXV. Always refer to the manufacturer's specifications for accurate measurements. Troubleshooting Using …2 low pressures with high superheat and low Subcool is a sign of what problem? Dirty Coil, Overcharged. Undercharged. Charged Properly. Overcharged. 48 of 54. Term. What are the 4 major components? Saturation temperature. Radiation. Conduction. Evaporator, condenser, compressor and metering device.Jan 22, 2023 · High superheat low subcooling on a TXV system means that there is no sufficient amount of refrigerant in the evaporator and there is low amount of the refrigerant in the condenser unit. This condition is mainly caused by low charge in an air conditioning system and can be fixed by sealing leaks and adequately charging the system with a refrigerant. The system actually works fairly well even on hot days, its just 2-3 degrees off the thermostat setting. The suction pressure is 95 PSI, about 28 degrees, but the superheat is normal, at 10. The liquid line pressure is fine, the outside coil is clean and the subcooling is 10, which is what the manufacturer calls for.Every 24 hours and 50 minutes, the Earth experiences two high tides and two low tides. High tides occur every 12 hours and 25 minutes. From high tide to low tide is a span of six h...Learn more on superheat and related topics here: Subcooling and Superheating: Easy Guide to Chilled Mastery. ... Low superheat is often caused by overfeeding the evaporator or high refrigerant levels. Like high superheat, it can cause problems and damage to your system. Reach out to a professional for assistance in resolving the issue.no superheat, no subcooling. Here is the situation... Design pressures are 150/300psi with 12 degree subcooling... Actual conditions are 92Psi liquid at a temperature of 69F. High pressure side is at around 220Psi and about 12F BELOW saturation temperature. Cooling isn't really doing much indoors and runs constantly.If your filter drier was plugged you would have low suction pressure and high superheat. This looks like something is going on internally and stopping your compressor from moving gas. ... When you have a receiver it's normal to have very low subcooling readings between 1 and 3 degrees. This more looks to be low compression if everything he ...Hey guys on package units where is the best place to place the temp clamps to get superheat/subcooling. I always place one of my clamps on the suction line 6" away from compressor. ... I was driven crazy by the Subcool readings on a Rheem package unit for days. Everything seemed to line up, and be in the right range except for my Subcool …Subcooling is a temperature below saturated pressure-temperature (Table 1). Subcooling is a measurement of how much liquid is in the condenser. In air conditioning, it is important to measure subcooling because the longer the liquid stays in the condenser, the greater the sensible (visible) heat loss. Low subcooling means that a condenser is empty.Low airflow typically not related to high superheat. High superheat and high subcooling often indicate a restricted metering device, since the evaporator would be starved and liquid refrigerant wouod be stacking up in the condenser. And if that was the case I don't think the unit would cool or dehumidify the house very well.Subcooling = 11F to 22F; Suction Superheat setpoint for 130-400 = 8F. Subcooling = 11F to 22F; These are measured at the king valve, chiller running at full load, and with all fans running; The subcooling values is based on 95 degree ambient; For high ambient conditions, subcooling will be closer to 11F. For low ambient conditions, subcooling ...Which line is the line temp taken and what is the state of the refrigerant for subcool. undercharged. Target is 10 degrees and actual is 5 degrees. Data plate. Where to find subcool target information. Study with Quizlet and memorize flashcards containing terms like Return air wet-bulb temperature and condenser ambient air dry-bulb temperature ...Low Superheat, High Subcooling. This usually means the system is overcharged. Low Superheat, Low Subcooling. This usually means too much liquid is being fed to the evaporator. Likely a problem with the metering device. All values are based on my current R22 system. Values may vary from system to system, always check manufacturer documentation.Suction PSI - Low. Superheat - High. Discharge PSI - Low. Subcool - High. Amps - Low. What is the problem? Low outdoor ambient. 3 multiple choice options. Study with Quizlet and memorize flashcards containing terms like Suction PSI - High Superheat - Low Discharge PSI - High Subcool - Low Amps - High What is the problem?, Suction …Over Charge- If refrigerant charge is high, the superheat will be low. The low side pressure will be higher than normal. This indicates the refrigerant did not absorb enough heat to properly change to a vapor. Liquid refrigerant may enter the compressor if superheat is too low. Dirty Evaporator Coil- A dirty air filter, evaporator coil or lack ...the superheat constant. Subcooling involves two measurements as well: one for pressure and one for temperature, but this one is taken from the liquid line. Target subcooling can be found on the system nameplate. The actual subcooling should be within ±3°F of the target subcooling for correct refrigerant charge. An improper …The most important values for checking to superheat and subcool are the endpoints of the glide or the pressure-temperature relationship for saturated liquid and saturated vapor. ... Some of the zeotropic blends have very low glide (from I° F to 2.5° F). For these blends, the vapor and liquid pressures are only separated by 1 or 2 psi. ...How to Calculate Superheat. 1. Obtain suction line temperature: First, measure the temperature of the suction line near the evaporator outlet using a digital thermometer or a clamp-on thermocouple. 2. Determine saturation temperature: Next, read the low side pressure gauge on your HVAC gauges while equipped with corresponding refrigerant scale ...Oh, and also, the pressures were not low. That and the high subcool makes me think it cannot be low on refrigerant just because the superheat is high. I think the other technician was correct. The condenser was dirty or there was a restriction. Adding refrigerant was not really the answer although it worked.An additional check of charge can be done by monitoring EXV Percent Flow Command and Superheat Control Compressor Flow Estimate in Kestrelview for the respective circuit. When properly charged, the ratio of EXV Percent Flow Command/Superheat Control Compressor Flow Estimate should be 1. If the ratio is 1.5 or greater, suspect low refrigerant chargeSuperheat is measured as the difference between the actual temperature of refrigerant vapor at a certain point and the saturation temperature of the refrigerant. It's not complicated, but for a beginning tech, it might be.". Superheat may be so complicated just because of the term "heat," Tomczyk said. "Because something can be minus ...With charging superheat gets very low and subcooling still low too for a TXV SYSTEM. Initial readings before charging : R-410A. Suction pressure 118 psig. Liquid pressure 330. Subcooling 0.9 degrees. Superheating 27 degrees. Suction line Temp 67 F. Liquid line Temp 102 F. After adding 3 lbs of Freon.When the subcool is set at 8C, the cooling capacity of DME is 6.5% lower than R134a but the COP is 2.6% higher. Another important finding in this study is that the best performance of DME over R134a is obtained at low subcool and low superheat.David Richardson. In the last Contracting Business HotMail article on Fundamentals of HVAC Superheat and Subcooling, we discussed these readings and …Troubleshooting low superheat. Low superheat values could result from an overcharged system, a dirty condenser coil, or a malfunctioning metering device. Think of it like diagnosing a car that's not running smoothly - you need to investigate and address the issue! Troubleshooting high subcoolingAt a high level, superheat occurs when you heat vapor above its boiling point. Subcooling occurs when you cool a vapor below the temperature at which it turns into a liquid. But let’s dive in deeper, starting with superheat. Boiling is when a liquid gains heat and transforms into a vapor. Remember, superheat occurs when you heat vapor above ...High subcooling is usually accompanied by high head pressure because liquid is displacing available condensing area. Low superheat, low evaporator load - dirty filter, slipping belt, low fan speed, filthy coil. High superheat, evaporators being starved for refrigerant if suction pressure is low. If suction pressure is high and superheat seems ...Buy HIATSU Digital Manifold Gauge HVAC Refrigeration Heavy Duty with 2 Wired Temperature High Low Side Pressure Measurement Superheat Subcooling 3 Hose Refrigeration Support 88 Types of Refrigerants: Air Conditioning Line Repair Tools - Amazon.com FREE DELIVERY possible on eligible purchasesCheck into superheat when the house is extremely warm will give you an inaccurate reading but your temperature drop should be 15 to 20 degrees. The more humid it is outside in the summer the lower your temperature drops going to be puts more load on the AC. I do a triple evac with nitro to remove non condensables.Jul 14, 2012 · Maryland. Posts. 9. Post Likes. Low Subcooling Low Superheat? I am working on a two stage heat pump with a varable speed air handler. The system runs about 1.5 deg S/C and about 2 deg S/H The delta T is 22 deg. A capacity check shows systems is operation at 122% of publish Capacity. Adding refregerant does not change the S/C much at all. I realize there is a calculation for your target superheat (eg. (IWB)*3-80-(OAT)/2=Target Superheat. However most units that I have come accross DO NOT specify the target subcooling (I speak of TXV/13 SEER units of course). I was wondering if anybody here knew of some calculation to determine this. I realize that 10 degrees will never get you in trouble, but I have read that fixed orifices can ...Superheat = Current Temperature - Boiling Point. Superheat is measured by its temperature above its boiling point. If a refrigerant vapor boiling point is 140 degrees, for example, then anything about that pressure would be too high for that specific refrigerant. To calculate the measurement of subcooling, the formula is: Subcooling = Boiling ...In today’s digital age, convenience is key. Whether it’s shopping for groceries or paying bills, more and more people are turning to online platforms to simplify their daily tasks....In this HVAC Video, I Explain Superheat and Subcooling in the Refrigeration Cycle to Understand the Operation Easier! I go over how to understand the importa...Low super heat, low subcool. Recovered some refrigerant out to reach target subcool but head pressure/superheat didn't get anywhere I wanted to. A/c was installed a month ago and charge was dialed in before leaving. Any ideas before I call tech support guy.never had this problemA low subcooling means that our condenser is mostly full of vapor, meaning the majority of the coil can be used to reject heat, a lower subcooling is preferable for efficiency, as your fan uses the same energy to reject the heat whether the coil is full of vapor or liquid, and we can't reject as much heat from the liquid as we can the vapor.Lowes is a well-known home improvement retailer that offers a wide range of products, including appliances. Whether you’re renovating your kitchen or looking to upgrade your curren...Starving the evaporator Increasing the system superheat Decreasing the system subcooling Increasing the operating head pressure and compression ratio Question 26 1. In general, air source heat pumps are sized to meet The building cooling capacity The sum of the building heating and cooling capacity Whichever is largest, the cooling capacity or ...Let’s take a look at other possible causes. Low suction pressure problems can be divided into two subcategories — low suction/high superheat and low suction/low superheat: Low suction/high superheat: Moisture, dirt, or wax buildup in critical areas, especially the metering device. In Figure 6, this fixed metering device is 30% blocked.Checking superheat will indicate if the low suction is caused by insufficient heat getting to the evaporator. To check superheat: 1. Attach a thermometer designed to …Low subcooling means that a condenser is almost empty. High subcooling means that a condenser is over field of liquid. 1) The amount of refrigerant entering the metering orifice is the Outdoor Dry bulb. 2) The total heat of the air entering the evaporator coil is the Indoor Wet bulb. With 95 degrees outside air.Low ambient temperature subcooling On an air cooled or water cooled chiller does subcooling decrease or increase with colder ambient temperature or colder water at the condenser? And if so please explain why Thanks 23-01-2017, 01:15 AM #2. The Viking. View Profile View Forum Posts ...Study with Quizlet and memorize flashcards containing terms like Low, Low, Low and more. ... Superheat is high. How is charge? Low. Subcool is low. How is charge? Low. Comp amps are low. How is charge? Low. Delta T is low. How is charge? Over. Suction pressure is high. How is charge? Over.Both are out of cooling. and both have high superheat. like suction 20psi -7F, suction line temp 78F, head pressure 190psi, 97F, liquid line temp 72F, out door dry bulb temp 73F, Wet bulb at register indoor 19F, indoor dry bulb temp at register 78F. At the start of the suction.low-pressure indoor wet-bulb suction-line condenser evaporator and Low-pressure gauge reads 67 psi, which corresponds to 39°F evaporating temperature. Superheat is 52° - 39° = 13°F. Superheat test: Superheat is the heat added to the evaporating vapor to ensure that no liquid enters the compressor. For a ˚xed-ori˚ce system this value ...Low subcooling means that a condenser is almost empty. High subcooling means that a condenser is over field of liquid. 1) The amount of refrigerant entering the metering orifice is the Outdoor Dry bulb. 2) The total heat of the air entering the evaporator coil is the Indoor Wet bulb. With 95 degrees outside air.Next in the series based on HVAC Refrigerant Diagnostic Quick Sheet Bryan talks Symptoms of Low Evaporator Airflow.Videos on Airflow from our friends at Tru ...Hi, I just put a new compressor on a gas pack. I charged it to the correct amount of refrigerant o the name tag. My ambient temp. is 100 degrees and the unit running with a high high side pressure a high suction pressure and high superheat and sub cooling. The indoor temp is 87 degrees. i was told that the high indoor temp is why my pressures and temps. are high.Subcooling is defined as the difference between the measured liquid temperature and the liquid saturation temperature at a given pressure. Total liquid subcooling occurs from the start of the 100% saturated liquid point in the condenser to the metering device. The saturated liquid temperature can be obtained from a pressure/temperature ...Subcooling should be 5-18 degrees, with higher values when the equipment has a TXV. Always refer to the manufacturer's specifications for accurate measurements. Troubleshooting Using Superheat and Subcooling Data. Low superheat: Indicates too much refrigerant in the evaporator, likely due to overcharging.Jul 25, 2021 ... 12:57. Go to channel · R-410A AC Unit Checked with Superheat: 4 Scenarios, Low Charge through Overcharged! AC Service Tech LLC•162K views · 10: ...If superheat is too low, it can indicate a floodback condition, which can lead to liquid refrigerant entering the compressor, potentially causing damage. What is the pressure at 85 degrees for 410A? At approximately 85 degrees Fahrenheit (29.4°C), the pressure for R-410A could be around 230-260 psi on the low side and 500-550 psi on …• High superheat if not designed for low-head pressure at TXV; • Low amp draw; • High subcooling. HIGH CONDENSER ENTERING AIR TEMPERATURE High ambients will have much different effects on an air conditioning system. The higher outdoor ambients will cause head pressure to elevate in order to complete the heat rejection task. The ...However, this time you consider the three main causes of low suction pressure and check superheat and subcooling to make the correct diagnosis. CAUSE #1: Insufficient heat getting to the evaporator. This can be caused by low airflow (e.g., dirty filter, slipping belt, undersized or restricted ductwork, dust and dirt buildup on blower wheel) or ...The saturation temperature on the low side was 28 degrees. I had a subcool of 20 and a superheat of 22. The delta T was 24F. The filter opening was 16X25 inches. The condenser coil look like it could use a cleaning. The fan amperage was 6.8.Feb 5, 2017 ... ... it means to have high superheated, low superheat high subcooling and low subcooling. I explain the other things that affect the superheat and ...Superheat = Current Temperature - Boiling Point. Superheat is measured by its temperature above its boiling point. If a refrigerant vapor boiling point is 140 degrees, for example, then anything about that pressure would be too high for that specific refrigerant. To calculate the measurement of subcooling, the formula is: Subcooling = Boiling ...A low subcooling and a high superheat. An air conditioner with a fixed restriction metering device is operating with an evaporator saturation temperature of 40 degrees Fahrenheit and a suction line temperature of 42 degrees Fahrenheit. The factory specified superheat for the current operating condition is 12 degrees Fahrenheit.May 22, 2021 · LOW SUPERHEAT LOW SUBCOOLING TXV. Low superheat indicates that there is an excess amount of refrigerant in the evaporator, or the heat load is not sufficient to vaporize the liquid refrigerant to vapor before it moves to the compressor resulting in compressor damage. Plugging of the evaporator coils can also result in low superheat. High superheat - refrigerant is boiling off faster in the evaporator, meaning the evaporator is starved. This leads to higher suction (vapor) temperature that can lead to overheating the compressor although that's rare. Typically caused by high heat load or undercharge. Low superheat - refrigerant is boiling slower in the evaporator, meaning ...Definition. Superheat hunting is a cyclical fluctuation in suction superheat due to a varying refrigerant flow rate in the system. Superheat hunting is the result of the expansion valve excessively opening and closing in an attempt to maintain a constant operating condition. Hunting can be observed as regular fluctuations in suction temperature ...This limits the amount of heat the refrigerant can absorb. In extreme cases, insufficient subcooling may even lead to the refrigerant converting back to its gaseous form before it ever reaches the evaporator coil. Perhaps the most common cause of insufficient subcooling is an abnormally low refrigerant charge.Part 1 of this article covered how to calculate total temperature glide, effective temperature glide, fractionation, average evaporator and condenser temperature, evaporator superheat, and condenser subcooling for refrigerant blends that have a temperature glide. This article will offer a quick review of evaporator superheat and condenser subcooling calculations, then create a scenario where a ...High superheat low subcooling on a TXV system means that there is no sufficient amount of refrigerant in the evaporator and there is low amount of the refrigerant in the condenser unit. This condition is mainly caused by low charge in an air conditioning system and can be fixed by sealing leaks and adequately charging the system with a refrigerant.Causes of High Superheat with Normal Subcooling Low Refrigerant Charge. Picture your HVAC system as a marathon runner. Just as runners need proper hydration, your system needs the right amount of refrigerant. A low refrigerant charge can cause high superheat, making your system work harder and less efficiently. ...Too low is when the liquid stops moving and becomes solid. But seriously, the lower the liquid temp entering the txv, The less energy is wasted to bring that liquid temp down to the evaporating temp. Eg: 55c entering txv down to -10c as it exits txv. Vs 35c to -10c. Or 45c down to -30c vs 25c down to to-25c.a txv is what maintains superheat for the evap coil. We have taken our superheat measurement. And should know if the superheat is very high no refrigerant is passing the txv. And if it's very low too much is passing. We can then test the txv bulb. Remove it from the system and hold it in your hand to warm it up watch the superheat go down.Currently: 30psig suction/55 superheat (47 if I check at evap) 330 psig head/50 subcool, sight glass clear. Outdoor ambient: 62. Freezer temp: 34 (working its way down) TD 5 degrees. I do have a significant layer of frost on the 3 dist tubes coming off of TXV.Liquid line temp 101 degrees and the suction was 49 degrees. The low subcooling and low suction pressure indicate low airflow. The somewhat low deltaT seems to contradict that. Could be a …Resetting the low-tire light on the Subaru Outback will turn the low-tire-pressure light off. Resetting can normally only be done properly with a diagnostic reset tool that you can...

A system with low superheat and high subcooling has too much refrigerant. The two previous conditions we looked at had high superheat. Low superheat shows too much refrigerant in the evaporator, and it cannot boil it off fast enough. The excess refrigerant could easily make it back to the compressor and cause permanent damage …. Cornell early decision release

low subcool low superheat

Suction PSI - Low. Superheat - High. Discharge PSI - Low. Subcool - High. Amps - Low. What is the problem? Low outdoor ambient. 3 multiple choice options. Study with Quizlet and memorize flashcards containing terms like Suction PSI - High Superheat - Low Discharge PSI - High Subcool - Low Amps - High What is the problem?, Suction PSI - Low ...Replace air filters and the blower wheel. Overfeeding of the metering device. Ensure sensing valve of the TXV is properly insulated. Insufficient heat load to the coil. Clean the filters and the coil. Oversized AC system. Consider going for a well Sized AC unit. Read also: How to Fix High Superheat Low Subcooling.In order to assure that liquid refrigerant does not return to the compressor during the running cycle, attention must be given to maintaining proper superheat at the compressor suction inlet. Emerson recommends a minimum of 20F (11C) superheat, measured on the suction line 6 inches (152mm) from the suction valve, to prevent liquid refrigerant ...162. 25. I know that having both high superheat and low subcooling on an Air-Conditioner (A/C) is a strong indication that an air-conditioner does not have enough refrigerant. When the charge on an A/C is low, there is less refrigerant that enters the evaporator. When there is a lower amount of refrigerant entering the evaporator, it takes less ...Low suction pressure, low superheat and low subcooling are a good indicator of poor airflow. Generally SH should be 10-15 and SC around 12. Now, once we establish airflow, next step is to confirm metering device - is it a piston or TXV? With a piston, we go by superheat. Add refrigerant to lower superheat or remove refrigerant to raise superheat.28. Post Likes. high super heat low suction. any ideas. I am working on a ruud heat pump. Freeze up problems. Low suction pressure, 24 superheat, 8 subcooling. 14 degree air drop across my coil. I have evacuated and wieghed in a charge r-22 and replaced txv. No kinks in line set and not a plugged filter dryer. .5 static pressure across my coil.Jan 28, 2023 · Low subcooling and high superheat are both conditions that can occur in a refrigeration system and indicate a problem with the system’s balance. Low subcooling means that there is an insufficient amount of refrigerant in the condenser, which is the part of the system where the refrigerant releases the heat it has absorbed from the evaporator. System Information R22 2.5 ton: Low Side: 115. High Side: 240. Return Air: 83. Suction Line Temp: 75. Measured Super heat: 5. Super heat should be around 15. Low superheat is an indication that liquid refrigerant not changing state in the evaporator and is possibly flooding back to the compressor.Yes, high superheat and low subcooling can harm your HVAC system. High superheat levels can cause the air conditioning system to deliver less cooling. It can also cause the compressor to overheat ...I had posted in a previous thread about the superheat reading taken on my system being about 11 *F too low (possible overcharge). Today another tech came out and measured everything again. This tech measured the subcooling as well this time. Here are the measurements he took: OAT DB: 68 *F Low side: 68 psi (39 *F) High side: 140 psi (78 *F) High side line temp: 71.7 *F Subcooling: 7 *F ...Next in the series based on HVAC Refrigerant Diagnostic Quick Sheet Bryan talks Symptoms of Low Evaporator Airflow.Videos on Airflow from our friends at Tru ...What causes low superheat. 5 ton Lennox XC13, low superheat 2 degrees, low subcooling that does not change when adding 1.5 lbs currently 4, required 9. Low suction and low head pressure, subcooling never changed with 1.5 lbs of 410a. Chart required charging by fixed orifice which I thought was weird. 85 outside, sat. temps were 34/92..